制作人:01/26/2025第1页序号设备名称1地上公共照明216.000.400.850.6286.4053.55101.65154.442地上应急照明72.000.400.850.6228.8017.8533.8851.483车库应急照明40.000.500.850.6220.0012.3923.5335.754弱电机房30.000.800.850.6224.0014.8728.2442.9056电梯432.000.220.551.5295.04144.32172.80262.5578配电房总配电箱20.000.800.850.6216.009.9218.8228.60合计810.00270.24252.90工程名称:XXX子项名称:地下室1号柴油发电机负荷统计(平时用)设备功率Pe(kW)需要系数Kx功率因数CosΦ功率因数的tanΦ有功功率(kW)无功功率(Kvar)视在功率(kVA)计算电流(A)制作人:01/26/2025第2页1270.24252.90370.121序号设备名称1一个单元的应急照明6.001.000.850.626.003.727.0610.732其余应急照明112.000.500.850.6256.0034.7165.88100.10390.000.800.800.7572.0054.0090.00136.7441.000.800.750.000.000.000.005消防泵200.001.000.850.62200.00123.95235.29357.5067地上一栋楼消防风机50.001.000.800.7550.0037.5062.5094.96一台消防电梯18.001.000.551.5218.0027.3332.7349.73同时系数K∑p=K∑q=1号柴油发电机负荷统计(消防时用)设备功率Pe(kW)需要系数Kx功率因数CosΦ功率因数的tanΦ有功功率(kW)无功功率(Kvar)视在功率(kVA)计算电流(A)地下室最大防火分区消防风机制作人:01/26/2025第3页合计476.00402.00281.211402.00281.21490.591序号设备名称1地上公共照明216.000.300.850.6264.8040.1676.24115.832地上应急照明72.000.300.850.6221.6013.3925.4138.613车库应急照明20.000.500.850.6210.006.2011.7617.884电梯432.000.180.551.5277.76118.08141.38214.81同时系数K∑p=K∑q=2号柴油发电机负荷统计(平时用)设备功率Pe(kW)需要系数Kx功率因数CosΦ功率因数的tanΦ有功功率(kW)无功功率(Kvar)视在功率(kVA)计算电流(A)制作人:01/26/2025第4页5生活水泵106.000.800.800.7584.8063.60106.00161.0650.000.700.850.620.000.000.000.006配电房总配电箱50.000.700.850.6235.0021.6941.1862.56合计896.00293.96263.110.9264.56249.96363.970.95序号设备名称1一个单元的应急照明6.001.000.850.626.003.727.0610.732其余应急照明62.000.500.850.6231.0019.2136.4755.41390.000.800.850.6272.0044.6284.71128.704一台消防电梯18.001.000.551.5218.0027.3332.7349.73同时系数K∑p=K∑q=2号柴油发电机负荷统计(消防时用)设备功率Pe(kW)需要系数Kx功率因数CosΦ...