主汽温度10min内下降超50℃跳机保护在SymphonyPlusS+系统的实现与应用刘伟(深能安所固(加纳)电力有限公司,广东深圳518000)摘要:按照《防止电力生产安全重大事故的二十五项重点要求》,电力企业应设置主汽温度10min内下降超50℃跳机保护,但是目前国内多数PG9171E型联合循环机组均未设置该保护。介绍了某厂SymphonyPlusS+系统用多种方式搭建该保护,且对搭建过程和应用环境进行了阐述,为其他电厂SymphonyPlusS+系统实现该功能提供参考和借鉴。关键词:SymphonyPlusS+;汽轮机;水冲击;温度中图分类号:TP29DOI:10.19768/j.cnki.dgjs.2023.02.004ImplementationandApplicationofTripProtectioninSymphonyPlusS+SystemwhentheTemperatureoftheMainSteamTurbineDropsOver50℃Within10MinutesLIUWei(ShennengAnsuogu(Ghana)ElectricPowerCo.,Ltd.,Shenzhen518000,China)Abstract:Accordingtothe"Twenty-fivekeyrequirementsforpreventingmajoraccidentsinpowerproductionsafety",powercompaniesshouldsetupthetripprotectionwhenthetemperatureofthemainsteamturbinedropsover50℃within10min.Thecaseofafactory'sSymphonyPlusS+systembuildingthisprotectioninavarietyofwaysisintroduced,andtheconstructionprocessandapplicationenvironmentareexplained.ThispaperprovidesreferenceforotherpowerplantstoimplementthisfunctionintheSymphonyPlusS+system.Keywords:SymphonyPlusS+;turbine;watershock;temperature收稿日期:2022-06-300引言某厂目前有2台汽轮机,分别为中国上海电气电站设备有限公司汽轮机厂生产的LZN55-5.60/0.65型55MW联合循环双压凝汽式汽轮机和中国南京汽轮电机(集团)有限责任公司生产的LZN60-5.80/0.58型60MW双压(带补汽)凝汽式联合循环汽轮机,DCS控制系统都是ABB的SymphonyPlusS+。现在许多国内9E级联合循环机组都没有主汽温度10min内下降超50℃跳机保护,但有人根据经验认为,此保护应该根据机组当前的主汽过热度来判断,即主蒸汽过热度大于100℃,在10min后即使下降50℃,主蒸汽过热度仍然超过50℃,此时没有必要设置该保护。但是实际上,这种认识是片面的。这是因为正常运行中,根据蒸汽压力换算,主蒸汽过热度都在150℃以上,如果过热度只要大于50℃就安全,那明显是错误的。大于50℃的蒸汽过热度已经接近湿饱和状态,随着降温减压,湿度将越来越大,如果不尽快采取停机升温手段,那么很可能导致汽轮机因水冲击而损坏严重。而且正常运行中蒸汽温度...